For the lintels to perform to the quoted loading figures and to meet the durability expectations included in this brochure, the following information MUST be adhered to:
1. Lintels damaged in transit should not be used.
2. Check the correct lintel is being installed.
3. All bearing areas should be prepared using full bricks/blocks or padstones.
4. Lintels should be installed with a minimum 150mm end bearing at both ends, be fully bedded on bricklaying
mortar and levelled both longitudinally and horizontally. When limited end bearings are unavoidable, check with
IG technical office for suitability.
5. Open back lintels should be filled with masonry in accordance with BS 5977 and a full block built in
through the end bearing and allowed to cure before continuing building.
6. The inner and outer leaves supported by the lintel should be raised together to avoid excessive eccentricity of
loading. Masonry above lintels should be allowed to cure before applying floor or roof loads, if this is not achievable, temporary support in the form of props should be used.
NHBC guidelines propose no greater than a 1m span for props during construction.
7. When installing concrete floor units or other heavy components, care should be taken to avoid shock
loading. Temporary support in the form of props is advisable if there is a limited amount of masonry to the
outer leaf. Pre-cast floor units should be laid on a mortar bed to avoid load concentrations at high points in the
masonry. Floor units should not be dragged into position.
8. Point loads should not be applied directly to lintel flanges. Lintels should have a minimum of 150mm
masonry between the flange and the application level of any form of loading.
9. In accordance with BS 5628 and NHBC requirements, all external wall lintels MUST be installed with a flexible damp proof course with the exception of those adequately protected by an eaves overhang or similar
form of protection. Stop ends should be provided as specified by BS 5628 Part 3 1985 and the NHBC to
avoid moisture entering the cavity near the reveals.
Proprietary stop ends should be used or alternatively the DPC should extend to the edge of the front toe and
50 - 150mm beyond the end of the lintel (depending on coursing) to allow formation of an integral stop end at a
suitable perp joint. Weepholes should be used in the external masonry leaf to drain moisture away from the
cavity. A minimum of 2 weepholes should be provided for each lintel, generally at 450mm centres. Weepholes can be formed with proprietary weep vents or by leaving perp joints open.
10. Masonry should not overhang any flange by more than 25mm.
11. The lintel toe must project beyond the window/door frame and it is recommended that a flexible sealing
compound is used between the underside of the lintel flange and the frame to avoid moisture penetration.
12. When the underside of a lintel is exposed, its appearance can be enhanced by the addition of lintel soffit cladding, supplied in white and brown, or by the application of a good quality etch primer and paint after installation.